Datalogic Controller SC6000 Manual do Utilizador Página 1

Consulte online ou descarregue Manual do Utilizador para Comutadores de rede Datalogic Controller SC6000. SC6000 Host Mode Programming (, 580249 byte) Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Host Mode Programming

SC6000Host Mode Programming

Página 2

SC6000 HOST MODE PROGRAMMING 6 2 HOST DEVICE <ESC> d M <B0H> 0 (Exit Programming Mode)<ESC> d <CR><LF> <ESC>

Página 3 - CONTENTS

PROGRAMMING STRINGS 7 33 PROGRAMMING STRINGS 3.1 DEFINITIONS Common definitions for each parameter are: Path The complete parameter path must hav

Página 4

SC6000 HOST MODE PROGRAMMING 8 3 Type (Parameter Type) Parameter type is essential in order to decide the parameter VALUE format used in the progra

Página 5 - 1 HOST MODE PROGRAMMING

PROGRAMMING STRINGS 9 3String (Type = 2) Length Minimum and maximum number of characters allowed for this parameter. Example: Device Name parameter

Página 6 - 2 PROGRAMMING COMMANDS

SC6000 HOST MODE PROGRAMMING 10 3 Floating Point (Type = 4) The Floating Point parameter value has the following format: XXX.YYY Range Minimum a

Página 7 - PROGRAMMING COMMANDS

PROGRAMMING STRINGS 11 33.2 HOW TO SEND SINGLE PARAMETER TO THE READER NOTE To guarantee the complete compatibility with future software releases,

Página 8 - 2.3 SELF DISCONNECTION

SC6000 HOST MODE PROGRAMMING 12 3 Using Short Parameter Description (Shortcut) The 'Set Shortcut' programming string (based on the short

Página 9

PROGRAMMING STRINGS 13 33.3 HOW TO GET SINGLE PARAMETER FROM THE READER NOTE To guarantee the complete compatibility with future software releases

Página 10 - SC6000 HOST MODE PROGRAMMING

SC6000 HOST MODE PROGRAMMING 14 3 Using Short Parameter Description (Shortcut) The 'Get Shortcut' programming string (based on the short

Página 11 - 3 PROGRAMMING STRINGS

PROGRAMMING STRINGS 15 33.4 HOW TO ACCESS INSTALLER PARAMETERS Set Right Parameter Description The 'Set Right' programming string allow

Página 12 - Enumeration (Type = 1)

Datalogic Automation Srl Via Lavino, 265 40050 - Monte S. Pietro Bologna - Italy SC6000 Host Mode Programming Ed.: 10/2012 This manu

Página 13 - Binary String (Type = 3)

SC6000 HOST MODE PROGRAMMING 16 3 3.5 SAVE AND RESTORE COMMANDS The 'Data Storage' programming command must have the following format:

Página 14 - Floating Point (Type = 4)

PROGRAMMING STRINGS 17 3The 'Restore Default Configuration' programming command must have the following format: SD<space>DEFNUM<C

Página 15 - PROGRAMMING STRINGS

SC6000 HOST MODE PROGRAMMING 18 3 HOST DEVICE SP<space>PATH1:VALUE1<CR><LF>(Set parameter 1) Y<space>VALUE1<CR><

Página 16

PROGRAMMING STRINGS 19 33.6 EXAMPLES - 1 - Set Minimum Label Length parameter in CODE LABEL SETTING #2 folder: Path: /Codes/Code#2/MinLength Shortc

Página 17

SC6000 HOST MODE PROGRAMMING 20 3 - 3 - Set Device Name parameter in USER INFORMATION SECTION folder: Path: /UserInfo/Name Shortcut: 522 Type: 2 (

Página 18

PROGRAMMING STRINGS 21 3- 5 - Get value of Digital Output 3 Activation Event parameter in DIGITAL OUTPUT LINES folder: Path: /IO/Out/Out2/Active Sho

Página 19

SC6000 HOST MODE PROGRAMMING 22 4 4 PARAMETERS LIST 4.1 CODE DEFINITION PARAMETER COMPLETE PATH SHC PT VALUE CODE DEFINITION Code Combination /

Página 20

PARAMETERS LIST 23 4PARAMETER COMPLETE PATH SHC PT VALUE Max Number of Different Characters /Codes/Filters /ContainedFilter NumberOfChar - 0 Range:

Página 21

SC6000 HOST MODE PROGRAMMING 24 4 PARAMETER COMPLETE PATH SHC PT VALUE Code Symbology /Codes /Code#N /Type 2 1 0 = Code 128 1 = Interleaved 2 of

Página 22

PARAMETERS LIST 25 4PARAMETER COMPLETE PATH SHC PT VALUE Max Code Position /Codes /Code#N /MaxCodePos 263 0 Range: 0 to 255 Check Digit /Codes /C

Página 23 - 3.6 EXAMPLES

iii CONTENTS 1 HOST MODE PROGRAMMING...1 2 PROGRAMMING COMMANDS

Página 24

SC6000 HOST MODE PROGRAMMING 26 4 PARAMETER COMPLETE PATH SHC PT VALUE Serial Stop String /Operating /SerialStop 87 3 Length: 1 to 32 Stop Inpu

Página 25

PARAMETERS LIST 27 4PARAMETER COMPLETE PATH SHC PT VALUE Minimum Pack Length (mm) /Operating /PktrMinLen 209 0 Range: 50 to 1000 Window Dimension

Página 26 - 4 PARAMETERS LIST

SC6000 HOST MODE PROGRAMMING 28 4 PARAMETER COMPLETE PATH SHC PT VALUE Max. Consecutive Delayed Codes For Node /Operating /ContEncMaxDelayOf Code

Página 27 - PARAMETERS LIST

PARAMETERS LIST 29 4PARAMETER COMPLETE PATH SHC PT VALUE Use Aux Serial Port /Operating /ProtocolIndexParameters /AuxPar/AuxEn - 1 0 = Disable 1

Página 28

SC6000 HOST MODE PROGRAMMING 30 4 PARAMETER COMPLETE PATH SHC PT VALUE Protocol Index Request Message /Operating /ProtocolIndexParameters /MainPar

Página 29 - 4.2 OPERATING MODES

PARAMETERS LIST 31 4PARAMETER COMPLETE PATH SHC PT VALUE Terminator /Operating /ProtocolIndexParameters /Eth1/PIUserSocket#N /StpSock - 3 Length:

Página 30

SC6000 HOST MODE PROGRAMMING 32 4 PARAMETER COMPLETE PATH SHC PT VALUE Protocol Index Request Message /Operating /ProtocolIndexParameters /Eth2/PI

Página 31

PARAMETERS LIST 33 4PARAMETER COMPLETE PATH SHC PT VALUE Field Separator /Operating/NVSHS/NVSRI /NVSFS - 3 Length: 0 to 1 Global Header /Operati

Página 32

SC6000 HOST MODE PROGRAMMING 34 4 PARAMETER COMPLETE PATH SHC PT VALUE Number of RFID Antennas /Operating/RBSHS /RBSNBSlaves - 0 Range: 0 to 4 S

Página 33

PARAMETERS LIST 35 44.3 READING SYSTEM LAYOUT PARAMETER COMPLETE PATH SHC PT VALUE READING SYSTEM LAYOUT Device Assignment /Layout/DevAssO 196 1

Página 35

SC6000 HOST MODE PROGRAMMING 36 4 PARAMETER COMPLETE PATH SHC PT VALUE EAN/UPC ADD ON 5 /Layout/SlvPar/CodPar /AddOn5 149 1 0 = Disable 1 = Enabl

Página 36

PARAMETERS LIST 37 4PARAMETER COMPLETE PATH SHC PT VALUE Decoding Severity /Layout/SlvPar/CodPar /Code93Par/DecSev 172 0 Range: 1 to 5 Ink Spread

Página 37

SC6000 HOST MODE PROGRAMMING 38 4 PARAMETER COMPLETE PATH SHC PT VALUE LONWORKS SINGLE SLAVES PARAMETERS (for backward compatibility) SLAVE NUMBER

Página 38

PARAMETERS LIST 39 44.4 DATA COMMUNICATION SETTING PARAMETER COMPLETE PATH SHC PT VALUE DATA COMMUNICATION SETTING Host Application Protocol Type /

Página 39 - 4.3 READING SYSTEM LAYOUT

SC6000 HOST MODE PROGRAMMING 40 4 PARAMETER COMPLETE PATH SHC PT VALUE Code EAN 13 Identifier String Comms/OutForm /codIDStr/codEAN13 404 3 Leng

Página 40

PARAMETERS LIST 41 4PARAMETER COMPLETE PATH SHC PT VALUE Termination String /Comms/OutForm /Standard/Terminator 7 3 Length: 0 to 128 Data Packet

Página 41

SC6000 HOST MODE PROGRAMMING 42 4 PARAMETER COMPLETE PATH SHC PT VALUE Termination String /Comms/CargoPar /Terminator - 3 Length: 0 to 128 S/W

Página 42 - /Layout/SngSlv/Slave#N

PARAMETERS LIST 43 4PARAMETER COMPLETE PATH SHC PT VALUE Diagnostic Data On Modem Serial Channel /Comms/CargoPar /OutMsg/DiagSerModem - 1 0 = Disa

Página 43

SC6000 HOST MODE PROGRAMMING 44 4 PARAMETER COMPLETE PATH SHC PT VALUE Including codes that start with '421…' /Comms/CargoPar /CarCodes

Página 44

PARAMETERS LIST 45 4PARAMETER COMPLETE PATH SHC PT VALUE MAIN SERIAL PORT Data Tx /Comms/SerMain /SerMain 510 1 0 = Disable 1 = Enable Heartbeat

Página 45

HOST MODE PROGRAMMING 1 11 HOST MODE PROGRAMMING An alternative method of programming the SC6000 Controller is by sending programming strings. Th

Página 46

SC6000 HOST MODE PROGRAMMING 46 4 PARAMETER COMPLETE PATH SHC PT VALUE Header n. 10 (Siemens RK512) /Comms/SerMain /Line/SRKHead10 - 3 Length: 1 F

Página 47

PARAMETERS LIST 47 4PARAMETER COMPLETE PATH SHC PT VALUE SW Release (Read-only) /Comms/Ethernet /System/Sw_release 91 2 Length: 0 to 10 MAC Addres

Página 48

SC6000 HOST MODE PROGRAMMING 48 4 PARAMETER COMPLETE PATH SHC PT VALUE Phase Echo /Comms/Ethernet /Services/EthernetIP /IO/In/PhaseEcho 295 1 0

Página 49

PARAMETERS LIST 49 4PARAMETER COMPLETE PATH SHC PT VALUE Max Conveyor Speed Percent Error (%) /Comms/Ethernet /Services/SentinelClient /ConvSpeedChe

Página 50

SC6000 HOST MODE PROGRAMMING 50 4 PARAMETER COMPLETE PATH SHC PT VALUE Protocol /Comms/Ethernet /Services/UserSocket#N /Protocol 137 1 0 = TCP 1

Página 51

PARAMETERS LIST 51 4PARAMETER COMPLETE PATH SHC PT VALUE Heartbeat /Comms/ProfiBus /Heartbeat - 1 0 = Disable 1 = Enable Unconditioned 2 = Enable

Página 52

SC6000 HOST MODE PROGRAMMING 52 4 PARAMETER COMPLETE PATH SHC PT VALUE ADDITIONAL ETHERNET / LINE PARAMETERS (Only -1230 Models) Status /Comms/Eth

Página 53

PARAMETERS LIST 53 4PARAMETER COMPLETE PATH SHC PT VALUE ADDITIONAL ETHERNET / SERVICES / WEBSENTINEL CLIENT Enable /Comms/Ethernet1 /Services/Sent

Página 54

SC6000 HOST MODE PROGRAMMING 54 4 PARAMETER COMPLETE PATH SHC PT VALUE Heartbeat Terminator String /Comms/Ethernet1 /Services/UserSocket#N /Heartb

Página 55

PARAMETERS LIST 55 4PARAMETER COMPLETE PATH SHC PT VALUE 5 = Australia 6 = Bolivia 7 = Bosnia-Herzegovina 8 = Brazil 9 = Brunei 10 = Bulgaria 11 = C

Página 56

SC6000 HOST MODE PROGRAMMING 2 2 2 PROGRAMMING COMMANDS 2.1 CONNECTION TO DEVICE DESCRIPTION HOST COMMAND REPLY MESSAGE 1 Enter Host Mode

Página 57

SC6000 HOST MODE PROGRAMMING 56 4 PARAMETER COMPLETE PATH SHC PT VALUE 58 = Senegal 59 = Serbia 60 = Singapore 61 = SlovakRep 62 = Slovenia 63 = S

Página 58

PARAMETERS LIST 57 4PARAMETER COMPLETE PATH SHC PT VALUE DIGITAL OUTPUT LINES / OUTPUT 1 Use /IO/Out/Out0/Use - 1 1 = Local 2 = Built-in Ethernet

Página 59

SC6000 HOST MODE PROGRAMMING 58 4 PARAMETER COMPLETE PATH SHC PT VALUE Activation Event /IO/Out/Out1/Active 24 1 0 = None 1 = Complete Read 2 =

Página 60 - 4.5 DIGITAL I/O SETTING

PARAMETERS LIST 59 4PARAMETER COMPLETE PATH SHC PT VALUE Alternative Activation Event /IO/Out/Out2/Active1 1 0 = None 1 = Complete Read 2 = Parti

Página 61

SC6000 HOST MODE PROGRAMMING 60 4 PARAMETER COMPLETE PATH SHC PT VALUE Deactivation Event /IO/Out/Out3/Deactive - 1 0 = None 7 = Timeout 5 = Ph

Página 62

PARAMETERS LIST 61 4PARAMETER COMPLETE PATH SHC PT VALUE Activate On Error /IO/Out/Out4 /ActiveDiagnoErr - 1 0 = Disable 1 = Any Diagnostic Error

Página 63

SC6000 HOST MODE PROGRAMMING 62 4 PARAMETER COMPLETE PATH SHC PT VALUE Deactivation Timeout (ms) /IO/Out/Out5/Timeout - 0 Range: 40 to 15000 RE

Página 64

PARAMETERS LIST 63 4PARAMETER COMPLETE PATH SHC PT VALUE Alternative Activation Event /IO/Relays/Relay1 /Active1 - 1 0 = None 1 = Complete Read 2 =

Página 65

SC6000 HOST MODE PROGRAMMING 64 4 PARAMETER COMPLETE PATH SHC PT VALUE Activate On Error /IO/Relays/Relay2 /ActiveDiagnoErr - 1 0 = Disable 1 =

Página 66

PARAMETERS LIST 65 4PARAMETER COMPLETE PATH SHC PT VALUE PackTrack Debug Message Digital Input /Diagno/PkTrDbg_Input - 1 0 = None 1 = PS 3 = PSAU

Página 67

PROGRAMMING COMMANDS 3 22.2 DISCONNECTION FROM DEVICE DESCRIPTION HOST COMMAND REPLY MESSAGE 1 Exit Programming Mode <ESC> d M <B0H&g

Página 68 - 4.7 DIAGNOSTICS

SC6000 HOST MODE PROGRAMMING 66 4 PARAMETER COMPLETE PATH SHC PT VALUE Presence Sensor Stuck Timeout /Diagno/PSStuck - 1 0 = Disable 1 = 1 sec

Página 69

PARAMETERS LIST 67 4PARAMETER COMPLETE PATH SHC PT VALUE Message Position /Diagno/Actions /SyncOpt - 1 0 = Append to Code 1 = Replace Code Aux /Di

Página 70

SC6000 HOST MODE PROGRAMMING 68 4 PARAMETER COMPLETE PATH SHC PT VALUE DIAGNOSTICS / SIMATIC RBS HYBRID SYSTEM ALARMS RFID System Connection Alarm

Página 71

PARAMETERS LIST 69 4Encoder Event Failure Filter /RedsPar/SwitchPar /EncoderFilterValue - 0 Range: 1 to 10 Check Max Consecutive Lost Parcels /Reds

Página 72 - 4.8 REDUNDANCY

SC6000 HOST MODE PROGRAMMING 70 4 PARAMETER COMPLETE PATH SHC PT VALUE Header /ES/ESAD/MainPar /ADStrMain - 3 Length: 0 to 1 Terminator /ES/ESAD/

Página 73 - 4.9 ENERGY SAVING

PARAMETERS LIST 71 4PARAMETER COMPLETE PATH SHC PT VALUE Activation String ES/ESAD/ADAddEth /ADUserSocket#N /ADActStringAddSock - 2 Length: 0 to 1

Página 74

SC6000 HOST MODE PROGRAMMING 72 A A SPECIAL COMMANDS AND TABLES CONTROL RULES TABLE This paragraph provides a list of the most important contro

Página 75

SPECIAL COMMANDS AND TABLES 73 APARAMETER CONTROL RULES DATA COMMUNICATION SETTING Host Application Protocol Type Must be  Crisplant if Operating

Página 76 - CONTROL RULES TABLE

SC6000 HOST MODE PROGRAMMING 74 A ERROR CODES TABLE This paragraph provides a list of the most important error codes. CODE INTERPRETATION COMMA

Página 77 - SPECIAL COMMANDS AND TABLES

SPECIAL COMMANDS AND TABLES 75 AASCII TABLE CHARACTER TO HEX CONVERSION TABLE CHAR HEX CHAR HEX CHAR HEX NUL 00 * 2A U 55 SOH 01 + 2B V 56 STX 02

Página 78 - ERROR CODES TABLE

SC6000 HOST MODE PROGRAMMING 4 2 2.3 SELF DISCONNECTION Specific situations exist where the device is automatically disconnected from the Host and

Página 79 - ASCII TABLE

www.automation.datalogic.com

Página 80

PROGRAMMING COMMANDS 5 2 HOST DEVICE <ESC> [ C (Enter Host Mode) <ESC> H <CR><LF> <ESC> ] B (Enter Terminal Mode)<E

Comentários a estes Manuais

Sem comentários